The Phoenix IR/UV IP-329/330-1-1 is Class 1 flame detector designed to detect ignitions involving electromagnetic radiation in the infrared (IR) and ultraviolet (UV) spectral ranges and equipped with a warning (emergency) alarm.
- Sensor type: infra-red and ultraviolet
- Supply voltage: 24 V (18 to 32 V)
- Power consumption: max 2.0 W
- Signal outputs: 4 to 20 mA, RS-485 Modbus RTU, dry contact relay modules
- Indication: color LEDs
- Fire protection type: flame detection
- Operating principle: optical
- Actuation: automatic
- Detection field of view: 90°
- Detection distance: up to 25 m
- Detection response time: 5 sec.
- Operating temperature range: -60°C to +120°C
- Type of protection: flameproof enclosure
- Explosion protection marking: 1Exd IIC T4
- Ingress protection: IP 66/68
- Seismic resistance MSK-64: 9 points
- Electromagnetic compatibility: 4th test severity level
- Lens heating
- Optical sensor contamination control
- Automatic diagnostics
- Event archiving: up to 800,000,000 events
- Built-in real time clock
- Special algorithm for protection against false alarms
- Enclosure material: aluminum, stainless steel
- Conduit connection: M20x1.5; M25x1.5; 3/4 NPT
The equipment is used in fire-hazardous and explosive zones, areas with technological equipment
of pumping stations, tank farms, gas distribution stations and gas processing units,
overpasses of discharge / filling of petroleum products and other facilities with an explosive nature of production
Questionnaire for ordering
Questionnaire for ordering stationary industrial explosion-proof flame detectors
Questionnaire for ordering stationary industrial explosion-proof flame detectors